Single Phase DIN Rail Power Supply 24V DC / 5A
POWER 1AC 24-5
Highly robust DIN rail Power Supply with built in remote ON/OFF functionality and signal output for confirming output voltage.
FunctionPrimary-switched power supply, 150% peak-power, RC-input, DC OK, input: 1-phase, output: 24 V DC / 5 A
Features- 150% Peak Power
- DC OK Relay Output
- Remote On/Off
- Full Function DIN Rail Power Supply
Additional Information
The full-featured DIN rail power supplies ensures superior system availability by means of new functions. The wide operating ambient temperature range and metal housing provides a robust usage in all industry applications. The power supply has a built in overcurrent protection and overvoltage protection circuits. The RC-input for stand-by can switch remote ON/OFF. For confirming output voltage the power supply indicates a green LED and a relay signal output.Input Data back to top
Input Voltage Range AC | 85 ... 264 V AC |
Input Voltage Range DC | 88 ... 370 V DC |
Input Current (typ.) | 0.6 A (230 V AC), 1.2 A (120 V AC) |
Frequency | 45 ... 66 Hz |
Efficiency (typ.) | 92 % (230 V AC), 90 % (120 V AC) |
Power Factor (cos φ) | 0.93 (230 V AC), 0.98 (120 V AC) |
Inrush Current (typ.) | 30 A (230 V AC), 15 A (120 V AC) |
Output Data back to top
Output Voltage | 24 V DC |
Output Voltage Range | 22.5 ... 28.5 V DC |
Output Current | 5 A |
Output Current (Peak Power) | 7.5 A |
Line Regulation | 96 mV |
Load Regulation | 150 mV |
Ripple (typ.) | 120 mVp-p |
Ripple Noise (typ.) | 150 mVp-p |
Temperature Regulation (typ.) | 240 mV |
Protection Circuit back to top
Overcurrent Protection | Works over 101% of peak current and recovers automatically |
Remote On/Off (RC) | Off = 4.5 ... 29.5 V DC |
DC OK Signalling | LED (Green) |
DC OK Contact | Relay contact 30 V DC 1 A max, 30 V AC 0.5 A max |
Alarm Signalling | LED (Red) |
Isolation back to top
Input/Output Isolation (at room temperature) | AC 3,000 V 1 minute, Cutoff current = 10 mA, DC 500 V 50 MΩ min |
Input/PE Isolation (at room temperature) | AC 2,000 V 1 minute, Cutoff current = 10 mA, DC 500 V 50 MΩ min |
Output/PE Isolation (at room temperature) | AC 500 V 1 minute, Cutoff current = 100 mA, DC 500 V 50 MΩ min |
Output/RC, DC OK Isolation (at room temperature) | AC 500 V 1 minute, Cutoff current = 100 mA, DC 500 V 50 MΩ min |
Ambient Condition back to top
Ambient Temperature (operating) | -25 ... +70 °C |
Ambient Temperature (start-up type tested) | -40 °C |
Ambient Temperature (storage/transport) | -40 ... +85 °C |
Operating Humidity (non-condensing) | 20 ... 90 % RH |
Storage Humidity (non-condensing) | 20 ... 90 % RH |
Vibration | 10 ... 55 Hz, 19.6 m/s² (2G), 3 minutes period, 60 minutes along Z axis (Non operating, mounted on DIN Rail) |
Impact / Shock | 196.1 m/s² (20G), 11 ms, once each X, Y and Z axis (Packing state) |
Degree of Protection | IP20 |
Operating Altitude (max. above sea level) | < 2000 m |
Mechanical Data back to top
Tightening Moment (min. / max.) | max. 1 Nm |
Housing | Metal |
Mounting DIN Rail according EN 60715 | TH35 |
Weight (typ.) | 580 g |
Cooling Method | Convection |
Lifetime back to top
MTBF (Telcordia) at 25°C | 2,183,409 h (100 % Load) |
MTBF (Telcordia) at 40°C | 1,104,451 h (100 % Load) |
MTBF (Telcordia) at 60°C | 446,917 h (100 % Load) |
Dimensions back to top
Width (mm) | 37 mm |
Depth (mm) | 117 mm |
Height (mm) | 124 mm |
Commercial Data back to top
Customs Tariff Number | 85044030 |
![](/_default_upload_bucket/206/image-thumb__206__feature_detail/peak-power.09548f03.png)
150% Peak Power
Up to 150% of rated current can be provided up to 5 sec. if needed.
![](/_default_upload_bucket/199/image-thumb__199__feature_detail/dc-ok-relay-en.48039c19.png)
DC OK Relay Output
If output voltage is decreasing the DC OK relay contact will open. In "normal" output voltage condition the relay contact is closed.
![](/_default_upload_bucket/198/image-thumb__198__feature_detail/dc-ok-led-en.74b64878.png)
DC OK LED
If output voltage is decreasing the DC OK LED turns off. In "normal" output voltage condition the LED is on.
![](/_default_upload_bucket/201/image-thumb__201__feature_detail/alarm-led-en_1.c6ab1d75.png)
Alarm LED signaling
If output voltage is decreasing the Alarm OK LED (Red) turns on. In "normal" output voltage condition the LED is off.
![](/_default_upload_bucket/207/image-thumb__207__feature_detail/remote-onoff-en.f8846f74.png)
Remote On/Off
连接一个外部直流电源并向远程 ON/OFF 连接器通电,可远程 ON/OFF 降低待机功率。 低电平(0 到 0.5V)或打开以打开电源,高电平(4.5 到 29.5V)关闭电源。
![](/_default_upload_bucket/262/image-thumb__262__feature_detail/efficiency-92-en_1.c601089a.png)
Efficiency up to 92%
Particularly efficient and thus cost- and resource-saving thanks to an efficiency of up to 92 %.
![](/_default_upload_bucket/202/image-thumb__202__feature_detail/full-feature-en.72c3f8cf.png)
Full Function DIN Rail Power Supply
Our high class Power Supplies are fully equipped with all valuable features.
![](/_default_upload_bucket/203/image-thumb__203__feature_detail/input-voltage-en.73a276a8.png)
Wide Input Voltage Range AC and DC
Input voltage range of the power supplies is from AC 85 V to AC 264 V or DC 88 V to DC 370 V.
![](/_default_upload_bucket/204/image-thumb__204__feature_detail/inrush-current.4e6f5d0d.png)
Built-in Inrush Current Limiting
Thermistor (POWER 1AC 24-5), thyristor technique (POWER 1AC 24-10) or active power relay circuit (POWER 1AC 24-20 / 48-10) is used in the inrush current limiting circuit.
![](/_default_upload_bucket/205/image-thumb__205__feature_detail/adj-output-en.17a7aa0d.png)
Adjustable Output Voltage with Potentiometer
To increase an output voltage, turn a built-in potentiometer clockwise. To decrease the output voltage, turn it counterclockwise.
![](/_default_upload_bucket/194/image-thumb__194__feature_detail/hiccup-mode-en.8bd1ff87.png)
Hiccup Operation Mode
Hiccup Operation Mode is a behavior of overload protection. In case of output overload or short circuit, the power supply switches off for a short time to restart cyclically (approximately in the range of seconds) again and again and to query the elimination of the overload.
![](/_default_upload_bucket/209/image-thumb__209__feature_detail/parallel_en.03fa09d5.png)
Parallel Operation
To increase availability you can use the Power Supply in parallel operation mode. Please use our POWER DIODE modules in this application.
![](/_default_upload_bucket/208/image-thumb__208__feature_detail/sieries-en.23c01525.png)
Series Operation
To increase the output voltage you can use the Power Supply in series operation.
![](/_default_upload_bucket/210/image-thumb__210__feature_detail/Slim-design-en.05360dae.png)
Ultra Slim Dimensions