Contact expansion module, 5 N/O, 1 N/C
SAFE-EXP
Contact expansion module with 5 safe relay contacts and 1 feedback contact
Designed in Germany
Produced in Germany
Function
5 safe relay contacts, 1 safe feedback contacts, up to SIL 3, 24 V DC, width: 22.5 mm
Features
Safe Extension Module
Single Channel Input
PL e, Category 4 (EN ISO 13849-1)
SIL CL 3 (EN 62061 / IEC 61508)
HAVE A QUESTION?
SKU/Order No.:
SA-SAFE-EX-50-00
Additional Information
SAFE-EXP is a safety relay to be used as a contact extension for a basic safety device up to SIL 3 and Cat. 4, PL e in accordance with EN 62061 / EN 61508 and EN ISO 13849. The feedback loop has to be integrated into main safety device. Single channel operation, automatic start, 5 safe relay contacts, 1 feedback contact nominal input voltage: 24 V DC, max. switching capacity 250 V AC / 6 A, pluggable screw terminal blocks
Standards and Regulations
back to top
In Compliance With
EN 60204-1; DIN EN ISO 13849-1; EN 62061
Rated Impulse Withstand Voltage (control voltage / contacts)
2.5 kV
Dielectric Strength
4 kV
Rated Insulation Voltage
250 V
Degree of Pollution
2
Overvoltage Category
3
Input Data
back to top
Nominal Operating Voltage
24 V DC
Input Voltage Range DC
21.6 ... 26.4 V
Power Consumption (max.)
2,3 W
Output Data
back to top
Safe Contacts (non delayed)
5 NO
Auxiliary Contacts (non delayed)
1 NC
Switching Voltage (max.)
250 V AC
Contact Rating AC (resistive load)
8 A (250 V, 2000 VA)
Contact Rating 230 V AC-15
5 A
Contact Rating DC (resistive load)
8 A (30 V, 240 W)
Contact Rating 24 V DC-13
5 A
Thermal Current per contact
Max. 15 A total (13-14, 23-24, 33-34)
Minimum Contact Load
5 V, 10 mA
External Fuses
10 A gG (NO)
Switch-on Delay (max.)
< 30 ms
Switch-off Delay (max.)
< 50 ms
Relay Contact Material
AgSnO2
Relay Contact Life (cycles)
1 x 10⁷
Mechanical Data
back to top
Wire Width
0.14 ... 2.5 mm²
Tightening Moment (min. / max.)
0.5 Nm / 0.6 Nm
Weight (typ.)
175 g
Mounting DIN Rail according EN 60715
TH35
Ambient Condition
back to top
Degree of Protection
IP20
Ambient Temperature (operating)
-15 °C ... +55 °C
Ambient Temperature (storage/transport)
-15 °C ... +85 °C
Operating Altitude (max. above sea level)
< 2000 m
Dimensions
back to top
Width (mm)
22.5 mm
Height (mm)
99 mm
Depth (mm)
114 mm
Commercial Data
back to top
Customs Tariff Number
8536411090
Safe Extension Module
To expand any application with additional 3 N/O safe contacts
Single Channel Input
Possible to wire single channel applications
PL e, Category 4 (EN ISO 13849-1)
TÜV certified up to PL e / Category 4
SIL CL 3 (EN 62061 / IEC 61508)
TÜV certified up to SIL 3
Housing with Plug-In Terminal Blocks
SAFE-EXP block diagram
SAFE-EXP as Expansion Module - Control with safe relay contacts
Wiring as contact extension of a basic device (Category 4, up to PL e / SILCL 3, if the safety output meets PL e / SILCL 3 and short circuits in line between the safety output and A1 of the SAFE-EXP can be ruled out)
Caution:
Safety contacts will be activated immediately by switching on the basic device.
Advice:
According to EN ISO 13849-2 the wiring has to be in a short-circuit - proof control cabinet with a minimum degree of protection of IP54. For example, EN ISO 13849-2, table D4 - Cables within an electrical installation space in accordance with EN 60204-1.
A feedback loop for monitoring the SAFE-EXP is necessary to achieve SIL 3 or PL e, this can be done by wiring the feedback to the auxiliary contact 61-62.
SAFE-EXP as Expansion Module - Control with safe PLC system
Wiring as contact extension of a safe PLC (Category 4, up to PL e / SILCL 3, if the safety output meets PL e / SILCL 3 and short circuits in line between the safety output and A1 of the SAFE-EXP can be ruled out)
Caution:
Safety contacts will be activated immediately by switching on the safe output of PLC.
Advice:
According to EN ISO 13849-2 the wiring has to be in a short-circuit - proof control cabinet with a minimum degree of protection of IP54. For example, EN ISO 13849-2, table D4 - Cables within an electrical installation space in accordance with EN 60204-1.
A feedback loop for monitoring the SAFE-EXP is necessary to achieve SIL 3 or PL e, this can be done by wiring the feedback to the auxiliary contact 61-62.
Frontlayout SAFE-EXP
Safety Characteristics according to EN ISO 13849-1
Load per contact AC 15 / DC 13
≤ 5A / ≤ 5A
Use duration T₁₀d [years]
20
Category
4
Performance Level PL
e