High‑efficiency 3-Phase DIN Rail Power Supply 24V DC / 40A

POWER 3AC 24-40

3-phase power supply with AC/DC input (320...600VAC/450...850VDC), 24VDC Output, 960W, 40A, Built-in DC OK relay contact, 150% peak load capability for 7s

功能

Three‑phase DIN‑rail power supply, 960 W, 24 VDC output, adjustable voltage, high efficiency, wide temperature range, complete protections, DC OK relay, parallel operation up to 4 units.

特点
  • 内置浪涌电流限制
  • 带电位器的可调输出电压
  • 功率提升 150
  • 并联操作
  • 超薄尺寸
有问题吗?

其他信息

The POWER 3AC 24-40 is a three‑phase AC/DC DIN‑rail power supply delivering 960 W at 24 VDC with an adjustable output range from 24 to 28 V and a rated current of 40 A, making it ideal for 24 V control, I/O, and drive systems. With a wide input range of 320...600 VAC (450...850 VDC), it supports global three‑phase grids and robust industrial environments. The unit achieves up to 95.5% efficiency, operates from −30 to +70 °C (start‑up at −40 °C), and provides a 20 ms hold‑up time to ensure stable DC power under fluctuating mains conditions. Integrated protection functions including over‑voltage, over‑current, short‑circuit, and over‑temperature with auto‑recovery, as well as enhanced conformal coating and a built‑in DC OK relay contact, increase system availability and diagnostics capability. For higher power requirements, up to four units can be connected in parallel with active current sharing to achieve up to 3840 W (3+1), while compliance with IEC/EN/UL 61010 and IEC/EN/UL 62368 safety standards and EMC class B emissions supports use in industrial control, semiconductor manufacturing, and renewable energy applications.

 

Parallel Use

POWER 3AC 24-40 has built-in active current sharing function and can be connected in parallel, up to 4 units, to provide
higher output power as exhibited below :
1. The power supplies should be paralleled using short and large diameter wiring and then connected to the load;
2. When parallel use, ensure that all P+ on the signal connectors of each power module are connected together,
and all P- also connected together;
3. Difference of output voltages among parallel units should be less than 0.2V.